High Efficiency Motors IE2
ABB’s General performance IE2 high efficiency motors are best suited for applications where simplicity and off the-shelf availability are paramount. With ABB quality and support these motors have the features appreciated by volume customers and serial OEM’s. Motors have IE2 efficiency.
Type: Three-phase squirrel-cage induction motors
Output: 0.37 kw to 630 kW*; 0.50 to 845 hp (According to IS 12615, IEC 60034-1, IS 325/1996)
Voltage: 415 V; 220 to 690 V
Duty: S1 to S8 acc. to IS: 12824
Ambient Temperature: 50 C; -20 C to 65 C
Altitude: Up to 1000 m, with Class F insulation
* IS 12615 specifies IE2 till 375kw.
General performance IE2 high efficiency motors Sizes 71 – 355
Dimension drawings
Premium Efficiency Cast Iron Motors IE3
ABB’s General performance IE3 Efficiency Motors are best suited for industries where quality, robustness and reliability are paramount. With ABB quality and support these motors have features appreciated by industry customers. Motors have IE3 efficiency. The robust, straightforward General performance IE3 motors meet all basic requirements and are available off-the-shelf. They are ideal for OEMs to build into pumps and fans, as well as for other applications including gearboxes, conveyors and general machinery. The extended range of variants provides considerable flexibility.
Motor Types : M2BAX
Output : 7.5 TO 355 KW
IEC FRAME SIZE : 132 TO 355
General performance IE3 efficiency cast iron motors Dimension drawings
Dimension drawings
Flame Proof Motors for Hazardous Environment – JHX
Introduction
The use of electrical motors in potentially explosive atmospheres is quite frequent these days. These motors have to be constructed in such a way that there is no risk of an explosion. An Explosion occurs when the following situations occur:
• Presence of potentially explosive atmosphere
• Existence of a source of ignition
• Possibility of transmission of the explosion
Classification of Hazardous Environment :
According to IS: 5572, Hazardous areas are classified in the following ways depending on the degree of probability of the presence of hazardous atmosphere.
Temperature Classes :
Combustible gas or vapour and explosion-protected electrical equipment are divided into temperature of the gas or to T6 with regard to the ignition temperature of the gas or vapour and the maximum surface temperature of the component.
Motor Types : M2BAX
Output : 7.5 TO 355 KW
IEC FRAME SIZE : 132 TO 355
Zone 2
Abnormal Conditions
Presence of explosive atmosphere only by accident, but not during normal duty ( 10 H per year)
Zone 1
Occasionally
Incidental presence of explosive atmosphere during normal duty (10 – 1000 H per year)
Zone 0
Continuously
Permanent presence of explosive atmosphere ( > 1000 H per year)
Zone – Criteria presence of gas
Zone 0 – Continuously of very long period
Zone 1 – Present in normal operations
Zone 2 – Unlikely, but if present, only for a short time
In Zone 0, no electrical motors can be installed. Most common motor for Zone 1 is the flameproof design, but it can also be used in Zone 2.
Application Groups:
Depending on the intended use, explosion-proof electrical operating equipment is divided into two major groups:
Group I – Equipment for coal mines (only specially designed motors for mines can be used)
Group II – Electrical equipment for use other than mines (surface industry)
Group II – motors with flameproof enclosures are still further divided into gas groups:
II A – Propane
II B – Ethylene
II C – Hydrogen
Flame proof motors, type “d”
ABB motors of flame proof design (type JHX) are TEFC, 3 phase squirrel cage induction motor (as per IS:2148 – 2004) for operation in hazardous location classified as Zone 1 and Zone 2 areas as per IS:5572
Note : Other frame sizes are available on request.
The motor enclosure has been designed in such a way that no internal explosion can be transmitted to the explosive atmosphere surrounding the machine. The enclosure must withstand, without damage, any pressure levels caused by an internal explosion, the shape, length and gap of part assembly joints at shaft opening, cable entries, etc.., shall be designed to allow for throttling and cooling of hot gases escaping outside. The standard emphasise the impact of an explosive atmosphere (for instance, explosion pressure) over constructional requirements of such apparatus.
Range : 0.25 ……. 15kW, 0.33 …..20hp
Frame : JHX71 …..JHX160 Pole:2 …..8
Features :
1. Motors suitable for high ambient temperature 50ºC.
2. Keeps an explosion which takes place inside the enclosure from propagating through gaps to the ambient.
3. Withstands the explosion pressure created inside the enclosures.
4. Benefits when dealing with special operating modes such as heavy stars and special applications.
5. All surface temperatures are selected to comply with the temperature class.
6. Suitability for use in temperature classes T1 toT4.
7. Can be used both in Zone 1 and Zone 2.
Dimension Drawing Flange Mounted Flame Proof Motors 71….160 Mounting Designation B5, V1, V3
Dimension Drawing Foot Mounted Flame Proof Motors 71….160 Mounting Designation B3, B6, B7, B8, V5, V6
Terminal Box